58
Part Two
Input3 Config Menu
Sup Venturi
MENU ITEM
SOFTWARE
NAME
ITEM DESCRIPTION
ITEM RANGE
DEFAULT
VALUE
Reset Calibration
Reset Cal
The Reset Cal item is used to return to the factory default
calibration, undoing any field calibration adjustments. When
this menu item is entered, the controller will prompt the
user to verify that they want to do this by displaying the
message “Are You Sure.” Entering YES resets the
K-Factor factor for this sensor to defaults. Entering NO will
cancel the reset.
None
N/A
Input3 Config Menu
Supply Switch
MENU ITEM
SOFTWARE
NAME
ITEM DESCRIPTION
ITEM RANGE
DEFAULT
VALUE
Low Flow Alarm
Signal
Low Flow Sig
The Low Flow Sig item sets the signal the Model RPC30
Room Pressure Controller will receive to indicate a low
supply flow condition when a sail, or other flow-proving,
switch is installed.
Open, Closed
Closed
Input4 Config Menu
Rm1 Dr Sw
MENU ITEM
SOFTWARE
NAME
ITEM DESCRIPTION
ITEM RANGE
DEFAULT
VALUE
Signal to Indicate
Open Door
Dr Open Sig
The Dr Open Sig item sets the signal the Model RPC30
Room Pressure Controller will receive to indicate a door is
open.
Open, Closed
Closed
Control Delay when
Closing Door
Freeze Delay
The Freeze Delay item sets the period of time the RPC30
Room Pressure Controller will wait to begin modulating
dampers to control room pressure differential after the door
is closed.
0 to 120 seconds
0 seconds