56
Part Two
Input3 Config Menu
Sup Lin Flow
MENU ITEM
SOFTWARE
NAME
ITEM DESCRIPTION
ITEM RANGE
DEFAULT
VALUE
Set Maximum
Sensor Output
Sensor Max
The Sensor Max item is used to set the maximum reading
of a flow station used to measure supply air flow. The
Sensor Max item has increments of 1000 ft/min.
0 to 10,000 ft/min
0
Set Minimum
Sensor Voltage
Output
Signal Min
The Signal Min item is used to set the minimum output
signal when a flow station and pressure transducer is used
to supply air flow.
0 to 10 V
0 V
Set Maximum
Sensor Voltage
Output
Signal Max
The Signal Max item is used to set the maximum output
signal when a flow station and pressure transducer is used
to supply air flow.
1 to 10 V
10 V
Reset Calibration
Reset Cal
The Reset Cal item is used to return to the factory default
calibration, undoing any field calibration adjustments. When
this menu item is entered, the controller will prompt the
user to verify that they want to do this by displaying the
message “Are You Sure.” Entering YES resets the
K Factor for this sensor to defaults. Entering NO will
cancel the reset.
None
N/A

Table of Contents

Other manuals for TSI Instruments PRESSURA RPC30

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the TSI Instruments PRESSURA RPC30 and is the answer not in the manual?

TSI Instruments PRESSURA RPC30 Specifications

General IconGeneral
BrandTSI Instruments
ModelPRESSURA RPC30
CategoryController
LanguageEnglish

Related product manuals