Technical Section
61
Input6 Config Menu
Ante Dr Sw
MENU ITEM
SOFTWARE
NAME
ITEM DESCRIPTION
ITEM RANGE
DEFAULT
VALUE
Signal to Indicate
Open Door
Dr Open Sig
The Dr Open Sig item sets the signal the Model RPC30
Room Pressure Controller will receive to indicate a door is
open.
Open, Closed
Closed
Input7 Config Menu
Rm1 Sup Tmp
MENU ITEM
SOFTWARE
NAME
ITEM DESCRIPTION
ITEM RANGE
DEFAULT
VALUE
Adjust Sensor
Calibration
Sensor Span
The Sensor Span item is used to adjust the calibration of
the supply air temperature sensor. The Sensor Span is an
offset adjustment and can only be adjusted by ±10°F.
-10°F to +10°F
0°F
Reset Calibration
Reset Cal
The Reset Cal item is used to return to the factory default
calibration, undoing any field calibration adjustments.
When this menu item is entered, the controller will prompt
the user to verify that they want to do this by displaying the
message “Are You Sure.” Entering YES resets the
Sensor Span factor for this sensor to defaults. Entering
NO will cancel the reset.
None
N/A
(continued on next page)