Parameters sub-menu (EF)
Parameter Explanation Options Function
dFL2 Switching delay of FL2
Only tye:
PS…LI2UPN…
PS…2UPN…
Adjustable range: 0 … 50 s in
increments of 0.1 s
(0 = delay time is not active)
dAP Damping of the switching
output (Filter)
Pressure peaks of short duration or
high frequency can be filtered.
(0 …4 s in increments of 0.01 s
0 = Filter is not-active)
dAA Damping of the analog
output
only type:
PS…-LI2UPN8X
PS…-LUUPN8X
Pressure peaks of short duration or
high frequency can be filtered.
(0 …4 s in increments of 0.01 s,
0 = delay time is not active)
P-n Switching output mode npn
pnp
NPN
PNP
diS Update of measuring
value on display
50 50 ms update
200 200 ms update
600 600 ms update
r50 50 ms update/display rotated
by 180°
r200 200 ms update/display rotated
by 180°
r600 600 ms update/display rotated
by 180°
OFF Measured value display not active.
Press the Set-button for temporary
display of measured value
rES Reset to the default state
SOF Software version
11.3
messages
Display Short description
SC1 short-circuit in output 1
SC2 short-circuit in output 2
SC12 short-circuit in both channels
boot EEPROM error

Table of Contents

Other manuals for turck PS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the turck PS Series and is the answer not in the manual?

turck PS Series Specifications

General IconGeneral
Brandturck
ModelPS Series
CategoryAccessories
LanguageEnglish

Related product manuals