15
Measurement close to a valve
Measurement close to a divergent.
Measurement close to a convergent.
V «Reflex» mode : Distance > (15x) the diameter of the pipe
/ «Direct» mode: Distance > (20x) the diameter of the pipe
V «Reflex» mode : Distance > (5x) the diameter of the pipe
/ «Direct» mode: Distance > (8x) the diameter of the pipe
V «Reflex» mode : Distance > (30x) the diameter of the pipe
/ «Direct» mode: Distance > (40x) the diameter of the pipe
V «Reflex» mode : Distance > (3x) the diameter of the pipe
/ «Direct» mode: Distance > (5x) the diameter of the pipe
V «Reflex» mode : Distance > (10x) the diameter of the pipe
/ «Direct» mode: Distance > (15x) the diameter of the pipe
V «Reflex» mode : Distance > (3x) the diameter of the pipe
/ «Direct» mode: Distance > (5x) the diameter of the pipe