DC Power Supply [DPG-30R & DPG-MC60R, DPG-MC120R, DPG-MC240R]
9
2-6. External control pin assignments
2-6-1. External control terminal (controller AD-IF connector)
When performing external control, see "Table 2-7 External control signal connection
equivalent circuits" and connect the external control terminal to an external control device such
as a PLC.
• When connected to the controller
Table 2-5 External control terminal pin assignments when connected to the controller
User interface analog signal common return
DC unit output voltage monitor signal *1
DC unit output current monitor signal *2
DC unit output power monitor signal *3
User Interface analog signal common return
ARC DELAY TIME setting on/off, on at low level
At low level, turns on DPG-30R output
Low level output when capable of output operation (low level also when
operating)
Low level output during output operation
Low level output while the DC unit is performing output at the set value
Low level output while an error is detected on the DC unit
Low level output during hard arc detection on the DC unit
Low level output during micro arc detection on the DC unit
User interface digital signal common return
User interface LEVEL signal common return
DC unit output setting voltage (0 to 10 V) *5
User interface analog signal common return
Sets the arc detection level by combination
150 V, 120 V, 90 V, 60 V, see 2-6-4
User interface digital signal common return
DC unit error reset (low active).Arc count reset on Controller
Changes the control mode by combination: constant power, constant
current, constant voltage
See 2-6-5
User interface digital signal common return
Apply 24 V from outside. 200mA or more
When the DC power supply panels are closed,output cable connected
and pin 37 INTERLOCK is on, low level output
At low level, interlock OK
0 to 1500 V for voltage level output 0 to 10 V.