DC Power Supply [DPG-30R & DPG-MC60R, DPG-MC120R, DPG-MC240R]
2. Overview
12
2-6-2. External control terminal supplementary description
The external control terminal wiring carries a risk of noise interference if the wiring is long. ULVAC
recommends the measures below.
1. recommends shielded twisted pair cables.
2. Isolate the signal on the external connection device-side with a photocoupler or other
component.
3. When routing the cables, do not bundle them with power lines.
4. establish the connection in the shortest wiring.
Signal levels
●Digital signals Digital signal input (DI) 24 V 5mA or more
Signals are active at low Digital signal output (DO) 24 V 5mA to 20mA/1ch
●Analog signals Analog signal input (AI) 0 to +10 V
Analog signal output (AO) Voltage 0 to 1500 V /0 to 10 V
Current 0 to 60 A * /0 to 10 V
Power 0 to 30 kW * /0 to 10 V
* Single unit values, changes by
multiplying by the number of units.
Table 2-7 External control signal connection equivalent circuits
Signal
type
Signal
Pin No
Equivalent circuit
DO
Digital
output
READY
11
COMD
PLC side
100Ω
DO
1000 p
27 V
DPG-MC60R,120R, 240R
AD INTERFACE side
OUTPUT
12
SETPOINT
13
DCFAIL
14
HARC
16
MARC
17
ERROR0
29
ERROR1
30
ERROR2
31
INT_ANS
36
DI
Digital
input
ARCDELAY
6
+24 V
IN
PLC side
2.2 kΩ
DI
DPG-MC60R,120R, 240R
AD INTERFACE side
6.8 V
DCON
10
ARC SET0
23
ARC SET1
24
RESET
26
P/I/V SELECT1
27
P/I/V SELECT2
28
INTERLOCK
37