4-42 1000 Series / Guide to Installation, Troubleshooting, and Maintenance
Table 4-14—Three-Phase Line Reactor Ratings (230 V)
Power
Current
Inductance
3.0%
Impedance
5.0%
Impedance
hp (kW)
A
rms
mH
mH
11/2
8
3.000
5.000
(1.1)
2
8
1.500
3.000
(1.5)
3
12
1.300
2.500
(2.2)
5
18
0.800
1.500
(3.7)
71/2
25
0.500
1.200
(5.5)
10
35
0.400
0.800
(7.5)
15
45 / 55
0.300
0.500
(11)
20
55
0.250
0.500
(15)
25
80
0.200
0.400
(18)
30
80
0.200
0.230
(22)
40
110
0.100
0.180
(30)
50
130 / 160
0.100
0.200
(37)
60
160
0.080
0.150
(45)
75
200
0.055
0.110
(55)