EasyManuals Logo

Unico 1105 User Manual

Default Icon
164 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #130 background imageLoading...
Page #130 background image
4-68 1000 Series / Guide to Installation, Troubleshooting, and Maintenance
Table 4-30Analog Interface Module Connections (CON2)
Terminal
Description
Bottom Row
CON2-1
Analog Input 4 (+)
CON2-2
Analog Input 4 (–)
CON2-3
Analog Input 5 (+)
CON2-4
Analog Input 5 (–)
CON2-5
Logic Common
CON2-6
Analog Input 6 (+)
CON2-7
Analog Input 6 (–)
CON2-8
Analog Input 7 (+)
CON2-9
Analog Input 7 (–)
CON2-10
Analog Output 3
CON2-11
Logic Common
CON2-12
Analog Output 4
Top Row
CON2-13
Analog Input 8 (+)
CON2-14
Analog Input 8 (–)
CON2-15
Analog Input 9 (+)
CON2-16
Analog Input 9 (–)
CON2-17
Logic Common
CON2-18
Analog Input 10 (+)
CON2-19
Analog Input 10 (–)
CON2-20
Analog Input 11 (+)
CON2-21
Analog Input 11 (–)
CON2-22
Analog Output 5
CON2-23
Logic Common
CON2-24
Analog Output 6
Inputs rated:
0 to 10 V DC or 0 to 20 mA
Impedance: 200 kΩ or 500 Ω
Outputs rated:
±10 V DC
Maximum output: 6 mA peak
Short circuit: 25 mA