Fault tracing vacon • 23
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
7
7.3 Other fault conditions
The following fault tracing diagram will help you to locate and fix some of the most usual problems.
If the problem persists contact your local distributor.
Figure 3. Fault tracing diagram for Modbus RTU
.
Check cabling
Check grounding
9330A.emf
No communication
Counter OK
Poor
communication
Check communi-
cation status (par.
Counter does not
run
Counter for bad
frames
increases
Check fieldbus
parameters
bus parameters in
menu
Check other field-
Check selected
protocol
Check termination
resistors
Check that both
ends of the fieldbus
line hav termi-
nation resistors
(chapter 4)
Check parameters
e
Is the device in
READY state?
Check Master’s
parameters
Is fieldbus selected
as control place?
Does Master give
RUN command?
Check cabling
Check termination
resistors
Other bus devices
Check connections
Check the led on
keypad
Check external
interlockings (I/O)
Check configura-
tions (Sla e add-
ress, baudrate etc.)
v
Check distances
between cables,
see chapter 4.
Check cable types,
see chapter 3.
Check grounding,
see chapter 4. Re-
member to make
grounding for each
device!
Check terminals for
loose connections
Check stripping of
cables and
conductors, see
chapter 4.
Use keypad to
monitor variable
Check that both
ends of th fieldbus
line have t rmina-
tion resistors
(chapter 4)
e
e
Check cable for
cuts
Check correct place-
ment of conductors
in terminals
Check other
necessary devices
Drive does not
start from the bus
Check control place
parameter setting
V2.1)

Other manuals for Vacon 20

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon 20 and is the answer not in the manual?

Vacon 20 Specifications

General IconGeneral
Communication OptionsModbus, CANopen, PROFIBUS, Ethernet
Protection ClassIP20
Power Range0.25 to 18.5 kW
Control MethodScalar control, Vector control
Ambient Temperature-10°C to +50°C

Related product manuals