3.2 Main incoming section
The main incoming section (MIS) includes the main incoming device. The main incoming device and
size is dependent on the required current of the complete line-up.
As standard the MIS section has the following equipment (see Figure 3):
1. Air circuit breaker
2. Mains connections
3. Digital multi instrument with field bus connection
4. Pre-charging components for AFE
As pre-engineered standard options we can provide the following:
Cabling from the top (+CIT)
Ground Switch (+ILE)
Current transducers (+ITR)
UL approved design and components (+NAR)
Arc detection (+ADU)
Cabinet heater (+ACH)
Cabinet light (+ACL)
+ILE requires an additional section.
Table 7. Available MIS sizes
MIS type Input current Width x Height x Depth (mm)
MIS_630 630 A 400 x 2000 x 605
MIS_800 800 A 600 x 2000 x 605
MIS_1000 1000 A 600 x 2000 x 605
MIS_1250 1250 A 600 x 2000 x 605
MIS_1600 1600 A 600 x 2000 x 605
MIS_2000 2000 A 600 x 2000 x 605
MIS_2500 2500 A 600 x 2000 x 605
MIS_3200 3200 A 800 x 2000 x 605
MIS_4000 4000 A 800 x 2000 x 605
MIS_5000 5000 A 800 x 2000 x 605