EasyManua.ls Logo

Vacon NXP series - Preparing the Installation Site; Free Space Around the Cabinet

Vacon NXP series
83 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation vacon • 31
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
4.2 Preparing the installation site
Before starting the installation work make sure that the level of the floor is within acceptable limits.
The maximum deviation from the basic level can be no more than 5 mm over a 3 m distance. The
maximum acceptable height difference between cabinet front and rear edges should be within
+2/-0 mm limit.
4.2.1 Free space around the cabinet
Enough space must be left above and in front of the cabinet to ensure sufficient cooling and space
for maintenance.
It is recommended to leave at least 200 mm above and 1000 mm in front of the cabinets.
Also make sure that the temperature of the cooling air does not exceed the maximum ambient
temperature of the drives.
Figure 12. Required space around the cabinet
200 mm
1000 mm
13860_00

Table of Contents

Other manuals for Vacon NXP series

Related product manuals