Release the input busbar assemblies. Remove:
1. two M10 nuts and M10x30 bolts (torque 40 Nm) from the upper busbars,
2. two M12 nuts and M12x40 bolts (torque 70 Nm) from the lower busbars,
3. two M8x20 screws (torque 20 Nm) from the back plate.
Take out the busbar assemblies, including the fuses.
Figure 36. Releasing the input busbar assembly
5
Release the output busbars. Remove three M10 nuts/bolts (tightening torque 40Nm).
Figure 37. Busbar mounting screws