Adapting the appliance to the heating system
Installation instructions geoTHERM 0020051574_04 91
9
Display shown Description Factory setting
Only if external passive cooling is installed:
Brine mixer = brine mixing valve in position
OFF, OPEN, CLOSED.
Cooling valve = Heating/cooling diverter valve in
position
OPEN = "Heating"
CLOSED = "Cooling"
Tool
A6
Component Test 2
Component VR 60 Addr. 4
Actuators OFF
Sensors VF a 29 °C
> select
T
his menu only appears if more than one heating cir-
cuit and at least one VR 60 are installed.
The component test 2 can be used to test the actua-
tors of the connected accessories. This intervention
lasts for a maximum of 20minutes and ignores cur-
rent controller inputs during this time. Afterwards, the
heat pump reverts to its previous operating condition.
Tool
A7
Venting prog OFF
Venting prog (VWS only): System venting pro-
gramme is started by inputting the value 30.
The brine pump alternates between 50minutes
operating and 10minutes off.
A connected circulation pump as well as the heating/
cylinder charging diverter valve and cooling diverter
valve (only if external passive cooling is installed) are
also
put into operation or switched.
Tool
A8
Calibration
Outside temperature 0.0K
DHW sensor SP 0.0K
VF2 flow sensor 0.0K
Buffer sensor RF1 0.0K
>Select correction value
¯
Tool
A8
Calibration
T buffer top <VF1> 0.0K
Display contrast 16
Manual adjustment of the displayed temperatures.
Offset adjustment range
Outside temperature: +/- 5 K, step size 1.0 K.
DHW sensor SP: +/- 3 K, step size 0.5 K.
VF2 flow sensor: The flow sensor VF2 is always dis-
played. +/- 3 K, step size 0.5 K.
Buffer sensor RF1: +/- 3 K, step size 0.5 K.
T buffer top <VF1>: +/- 3 K, step size 0.5 K.
Internal sensors can only be changed via vrDIALOG or
vrnetDIALOG, and buffer and cylinder sensors only
with the appropriate hydraulics.
Display contrast: Setting the display contrast
(0 – 25).
0 K
0 K
0 K
0 K
0 K
16
9.9 Menu A: Calling up Installation Assistent

Table of Contents

Other manuals for Vaillant geoTHERM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vaillant geoTHERM and is the answer not in the manual?

Vaillant geoTHERM Specifications

General IconGeneral
BrandVaillant
ModelgeoTHERM
CategoryHeat Pump
LanguageEnglish

Related product manuals