VAMP Ltd
Over-, under-, residual voltage and
frequency relay
Technical description
VAMP 135
VM135.EN008 VAMP 24h support phone : +358 (0)20 753 3264
27
4.3. Output relays
The VAMP 135 relay is equipped with five configurable output
relays and a separate output relay for the self-supervision
system, Figure 4-1.
•
Trip relays T1 and T2 (terminals X2: 19 - 20 and 16 - 17)
•
Alarm relays A1 - A3 (terminals X2: 13 - 14, 11 - 12 and 9 -
10)
•
Self-supervision system output relay IF (terminals X2: 7 - 8)
•
The trip relay T2 can also be used for alarm purposes.
4.4. Serial communication connections
•
RS 232 serial communication connection for computers,
connector LOCAL (RS 232), connector on the front panel of
the relay
•
Remote control connection, connector REMOTE (TTL) on
the rear panel of the relay (terminal X5), Figure 4-1. See
also Table 2.6.2-1.
4.5. Voltage transducer
•
The output signal, i.e. 0 - 20 mA or 4 - 20 mA, of the
integrated mA transducer is available on terminal X2: 1 - 2.
•
Polarity: +=X2:1, -=X2:2
Available couplings to the analogue output
•
U12, U23, U31, Uline
•
UL1, UL2, UL3
•
U
0
•
U2/Un
•
f