EasyManua.ls Logo

VAMP 135 - Undervoltage Protection U<, U<<, U<<< (27)

VAMP 135
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VAMP 135 Over-, under-, residual voltage and
frequency relay
Technical description
VAMP Ltd
10
VAMP 24h support phone : +358 (0)20 753 3264
VM135.EN008
Overvoltagefault
U>start
U>>start
U>trip
U>>trip
ALARM
TRIP
Figure 2.3.1-3. A settable start time is obtained by combining two protection
stages.
A settable start time is obtained by combining two protection
stages. Both stages detect the overvoltage, but the start signals
are ignored. The trip signal of stage U> is used as an alarm
signal and trip information from stage U>> is used for the
actual trip. The overvoltage setting value for stage U>> has to
be higher than the setting value for stage U> to ensure an
alarm before trip.
During a short circuit or an earth-fault, breaker Q1 performs
an auto-reclose. Breaker Q2 has to be tripped before the auto-
reclose of breaker Q1 to ensure that the generator does not
continue to feed the fault.
Parameters of the overvoltage stages: U>, U>>, U>>> (59)
Parameter
ParameterParameter
Parameter
Va
VaVa
Value/unit
lue/unitlue/unit
lue/unit
Measured
value
U>, U>>,
U>>>
V Max. value of line voltages
U12 to U31 primary values
U>, U>>,
U>>>
% Setting value in relation to the
rated voltage Un
t>, t>>,
t>>>
s Operation time
ReleaseDly s Release delay [s] (only U>)
Setting
values
Hysteresis % Deadband (only U>)
SCntr Start counter (Start) reading Recorded
values
TCntr Trip counter (Trip) reading
2.3.2. Undervoltage protection U<, U<<, U<<< (27)
The three-phase undervoltage unit comprises three separately
adjustable undervoltage stages (stage U<, U<< and U<<<).
The undervoltage unit measures the fundamental frequency
component of the line voltages. The protection stages operate
with definite time characteristics.

Table of Contents

Related product manuals