6 Set up with the display and adjustment module
FIBERTRAC 31 • Probus PA
43833-EN-170126
Peak values of measured value: Resetting of the parameter adjust-
ments in the menu item "Setup" to the default values of the respective
instrument. Order-specic settings remain but are not taken over into
the current parameters.
Peak values of temperature: Resetting of the measured min. and
max. temperatures to the actual measured value.
The following table shows the default values of the instrument. The
values apply for the application "Level". First of all you have to select
the application.
Depending on the instrument version, not all menu items may be
available or they may be dierently assigned:
Menu Menu item Default value
Setup Sensor address 126
Measurement loop name Sensor
Isotope Cs-137
Application Level
Background radiation
0 ct/s
Unit of the process value %
Temperature unit
° C
Adjustment min. Min. process value = 0 %
Adjustment max. Max. process value = 100 %
Linearisation 0 ct/s = 100 %
90000 ct/s = 0 %
AI FB1 Channel Process value
AI FB1 scaling unit %
AI FB1 scaling
0 % = 0 %
100 % = 100 %
AI FB1 damping 0 s
Damping 60 s
Real value correction 0
Reference value - Relay None
Lock adjustment Released
Display Language Selected language
Displayed value Pulse rate (ct/s)
With this function
Load parameter adjustment data from the sensor into the display
and adjustment module
Write parameter adjustment data from the display and adjustment
module into the sensor
Additional settings - Copy
instrument settings