EasyManua.ls Logo

Vega VEGAFLEX 86 - Page 10

Vega VEGAFLEX 86
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
3 Product description
VEGAFLEX 86 • Probus PA
44232-EN-160518
TS
d1
h1
h2
d2
1
L2
L1
L3
Fig. 3: Interface measurement
1 Sensorreferenceplane(sealsurfaceoftheprocesstting)
d1 Distance to the interface
d2 Distance to the level
TSThicknessoftheuppermedium(d1-d2)
h1 Height - Interface
h2 Height - Level
L1 Lower medium
L2 Upper medium
L3 Gasphase
Upper medium (L2)
The upper medium must not be conductive
The dielectric constant of the upper medium or the actual distance
to the interface must be known (input required). Min. dielectric con-
stant: 1.6. You can nd a list of dielectric constants on our home
page: www.vega.com.
The composition of the upper medium must be stable, no varying
products or mixtures
The upper medium must be homogeneous, no stratications
within the medium
Min. thickness of the upper medium 50 mm (1.97 in)
Clear separation from the lower medium, emulsion phase or detri-
tus layer max. 50 mm (1.97 in)
If possible, no foam on the surface
Lower medium (L1)
The dielectric constant must be 10 higher than the dielectric
constant of the upper medium, preferably electrically conductive.
Example: upper medium dielectric constant 2, lower medium at
least dielectric constant 12.
Gas phase (L3)
Air or gas mixture
Gas phase - dependent on the application, gas phase does not
always exist (d2 = 0)
Prerequisites for inter-
face measurement

Table of Contents

Other manuals for Vega VEGAFLEX 86

Related product manuals