3 Product description
VEGAFLEX 86 • Probus PA
44232-EN-160518
You can nd additional information in the operating instructions
manual "Externalhousing" (Document-ID 46802).
If you are using an instrument with rod version, you can extend the
rod probe individually with curved segments and rod and cable exten-
sions of dierent lengths.
All extensions used must not exceed a total length of 6 m (19.7 ft).
The extensions are available in the following lengths:
Rod: ø 16 mm (0.63 in)
•
Basic segments: 20 … 5900 mm (0.79 … 232 in)
•
Rod/cable segments: 20 … 5900 mm (0.79 … 232 in)
•
Curved segments: 100 x 100 mm (3.94 … 3.94 in)
You can nd further information in the operating instructions manual
"RodandcablecomponentsVEGAFLEX80series".
The combination of a bypass tube and a VEGAFLEX 86 enables con-
tinuous level measurement outside the vessel. The bypass consists
of a standpipe which is mounted as a communicating container on
the side of the vessel via two process ttings. This kind of mounting
ensures that the level in the standpipe and the level in the vessel are
the same.
The length and the process ttings can be congured individually. No
dierent connection versions available.
You can nd further information in the operating instructions manual
"
BypasstubeVEGAPASS81".
If you mount the VEGAFLEX 86 in a bypass tube or standpipe, you
have to avoid contact to the bypass tube by using a spacer at the
probe end.
You can nd additional information in the operating instructions
manual "Centering".
If there is a risk of the cable probe touching the vessel wall during
operation due to product movements or agitators, etc., the measuring
probe can be strained.
Cables with a diameter up to 8 mm (0.315 in) can thus be strained.
For this purpose there is an internal thread (M12 or M8) in the gravity
weight.
Rod components
Bypass tube
Centering
Fixing facility