9 Adjustment menu
VEGAPULS 11 • Two-wire 4 … 20 mA
58350-EN-200806
9 Adjustment menu
9.1 Menu overview
Menu item Selection Basic settings
Measurement loop
name
Alphanumeric characters Sensor
Medium Liquid
Bulk solid
Liquid
Application liquid Storage tank, agitator tank, dos-
ing tank, pumping station/pump
shaft,rainoverowbasin,tank/
collection basin, plastic tank
(measurement through tank
top), mobile plastic tank (IBC),
level measurement in waters,
owmeasurementume/over-
ow,demonstration
Storage tank
Application bulk solid Silo (slim and high), bunker
(large volume), stockpile (point
measurement/proledetection),
crusher, demonstration
Silo (slender and
high)
Units Distance unit of the device
Temperature unit of the instru-
ment
Distance in m
Temperaturein°C
Adjustment Max. adjustment (distance A)
Min. adjustment (distance B)
Max. adjustment
8,000 m
Min. adjustment
0,000 m
Menu item Selection Basic settings
Damping Integration time
0 s
Current output Output characteristics 4 … 20 mA
Current range Min. current 3.8 mA
and max. current
20.5 mA
Reaction when malfunctions
occur
Failure mode
< 3.6 mA
Linearisation Linearization type Linear
Scaling Scaling size
Scaling unit
Scaling format
0 % correspond to 0 l
100 % correspond
to 100 l
Display Menu language
Displayed value
Backlight
English
Filling height
On
Access protection Bluetooth access code -
Main menu