36
10 Diagnostics and servicing
VEGAPULS 11 • Two-wire 4 … 20 mA
58350-EN-200806
41 2 3
Fig. 22: Pictographs of the status messages
1 Failure - red
2 Outofspecication-yellow
3 Function check - orange
4 Maintenance required - blue
Failure: Due to a malfunction in the instrument, a fault message is
output.
This status message is always active. It cannot be deactivated by the
user.
Function check: The instrument is being worked on, the measured
value is temporarily invalid (for example during simulation).
This status message is inactive by default.
Outofspecication: The measured value is unreliable because an
instrumentspecicationwasexceeded(e.g.electronicstemperature).
This status message is inactive by default.
Maintenance required:
Duetoexternalinuences,theinstrument
functionislimited.Themeasurementisaected,butthemeasured
value is still valid. Plan in maintenance for the instrument because a
failure is expected in the near future (e.g. due to buildup).
This status message is inactive by default.
Code
Text message
Cause Rectication
F013
no measured value
available
No measured value in the switch-on
phase or during operation
Check or correct installation and/or pa-
rameter settings
Clean the antenna system
F017
Adjustment span too
small
Adjustmentnotwithinspecication Change adjustment according to the limit
values(dierencebetweenmin.andmax.
≥10mm)
F025
Error in the lineariza-
tion table
Index markers are not continuously rising,
for example illogical value pairs
Check linearization table
Delete table/Create new
F036
No operable software
Checksum error if software update failed
or aborted
Repeat software update
Send instrument for repair
F040
Error in the electronics
Limit value exceeded in signal processing
Hardware error
Restart instrument
Send instrument for repair
F080
General software error
General software error Restart instrument
Failure