10.3 Diagnosis, fault messages
Connect a multimeter in the suitable measuring range according to
the wiring plan. The following table describes possible errors in the
current signal and helps to eliminate them:
Error Cause Rectication
4 … 20 mA signal not stable Fluctuating measured value Set damping
4 … 20 mA signal missing Electrical connection faulty Check connection, correct, if necessary
Voltage supply missing Check cables for breaks; repair if nec-
essary
Operating voltage too low, load resist-
ance too high
Check, adapt if necessary
Current signal greater than
22 mA, less than 3.6 mA
Sensor electronics defective Replace device or send in for repair de-
pending on device version
The LED illuminated ring on the device (see chapter " Conguration")
indicates the operating status of the device. This enables simple on-
site diagnosis without the need for tools.
Colour
3)
Permanent light Flashing
Green Operation without interference Message " Maintenance required" is
displayed
Yellow Operation without interference -
Red Operation with interference
Message acc. to to NE 107 " Function
check", " Outofspecication" or " Simu-
lation state" is displayed
10.4 Status messages according to NE 107
The instrument features self-monitoring and diagnostics according
to NE 107 and VDI/VDE 2650. In addition to the status messages in
the following tables there are more detailed error messages available
under the menu item " Diagnostics" via the respective adjustment
module.
The status messages are divided into the following categories:
•
Failure
•
Function check
•
Outofspecication
•
Maintenance required
and explained by pictographs: