About Advanced Features & Operation
29
Deadband Operation
Controls up to two Heat and two Cool stages.
The 1st Stageofheatorcoolisturnedonwhen:
(A)Thetemperaturespreadfromthesetpointisequaltoorgreater
than:the setpoint plus the 1st stage deadband.This1ststagedead-
bandisadjustablefrom1-6degreesandthedefaultistwodegrees.
The 2nd Stageofheatorcoolisturnedonwhen:
(A)The1stStagehasbeenonforaminimumoftwominutes
(defaultsetting).
AND
(B)Thetemperaturespreadfromthesetpointisequaltoorgreater
than:the setpoint plus the 1st stage deadband, plus the 2nd stage
deadband.This2ndstagedeadbandisadjustablefrom0-10
degrees.