Dry Contact Use (Setup Step 25 )
Condensate Pan - If selected when the
DryContactisactive,thethermostat
willlockoutcompressorterminal(s)and
“CONDENSATEPAN”willappearonthe
display.
Vacation-IfVacationisselectedwhenthedrycontactisactive,
thethermostatwillbeforcedintoAWAY/Unoccupiedsettings.
FDD - IfFDDisselectedwhenthedrycontactisactive,“EQUIP
FAULT”willappearonthedisplay.
Dry Contact Operation
Dry Contact Polarity (setup step 24)
Open (Normally Open)-Thedry
contact is open until the connected
deviceclosesthecircuit.
Closed (Normally Closed)-The
dry contact is closed until the
connecteddeviceopensthecircuit.
Dry
Contact
‘Idle’ ‘Active’
Dry
Contact
Dry
Contact
‘Idle’ ‘Active’
Dry
Contact
Dry
Contact
‘Idle’ ‘Active’
Dry
Contact
Dry
Contact
‘Idle’ ‘Active’
Dry
Contact