Advanced Setup Table
34
FD = Factory Default Setting
Step# Description Pg# Range FD
1 Set Clock 17 12A - 12A
2 Set Day of Week 17 Monday - Sunday
3 Backlight 18 On, Off, 6pm-6am Off
4 Night Dimmer 18 On/Off Off
5 Night Dimmer Start Time 18 12A - 12A 8:00PM
6 Night Dimmer Stop Time 18 12A - 12A 6:00AM
7 Current Service Filter Runtime Hours 19 0-1999 Hours 0
8 Current Service Filter Calendar Days 19 0-720 Hours 0
9 Set Service Filter Runtime Hours 19 0-1999 Hours 0
10 Set Service Filter Calendar Days 19 0-720 Days 0
11 Setpoint Limits 20 On, Off Off
12 Maximum Heat Setpoint Limit 20 35 - 99 Degrees 74
13 Minimum Cool Setpoint Limit 20 35 - 99 Degrees 70
14 Cycles Per Hour 21 No Limit, 2, 3, 4, 5, 6 6
15 Compressor Minimum Off Minutes 21 0, 3, 5 Minutes 5
16 Min. Heat/Cool Setpoint Difference 21 0 - 6 Degrees 2
17 1st Stage Deadband 22 1 - 6 Degrees 2
18 2nd Stage Deadband 22 0 - 10 Degrees 2
19 Minutes Between 1st and 2nd Stage 22 0 - 60 Minutes 2
20 2nd StageTurnoff Point 22 Deadband, Setpoint Deadband
21 Fan Off Delay 23 0, 120 Seconds 0
22 F/C 23 Fahrenheit(F),Celsius(C) F
23 Comfort Recovery 23 On, Off Off
24 Dry Contact Polarity 24 Open, Closed Open
25 Dry Contact Use 24 CondensatePan,Vacation,FDD Vacation
26 Skyport 25 On, Off On
27 Local API 25 On, Off Off
28 Available Modes 25 Heat,Cool,HeatorCool,Auto Auto
29 Show Clock 25 On, Off On
TO ENTER MENUS BUTTON PRESS
SetupSteps .......................... MODE&FANfor5seconds
TimeSchedule ..................... MODE&Upfor2seconds
EmergencyHeat .................. Up&FANfor2seconds
LockoutButtons ................... MODE,Up&Downfor2seconds
Calibration ............................. MODE&Downfor2seconds
WirelessSetup .................... FANfor5Seconds
Table for button
presses that are
required for
enteringvarious
menus