EasyManuals Logo
Home>Vertiv>Switch>Avocent MergePoint Unity

Vertiv Avocent MergePoint Unity User Manual

Vertiv Avocent MergePoint Unity
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #70 background imageLoading...
Page #70 background image
6.0.11 Cabling installation, maintenance and safety tips
The following is a list of important safety considerations that should be reviewed prior to installing or
maintaining your cables:
Keep all UTP runs to KVM IQ modules to a maximum of 50 meters each.
Keep all UTPruns to serial IQ modules a maximum of 30 meters each.
Maintain the twists of the pairs all the way to the point of termination, or no more than one-half
inch untwisted. Do not skin off more than one inch of the jacket while terminating.
If bending the cable is necessary, make it gradual with no bend sharper than a one inch radius.
Allowing the cable to be sharply bent or kinked can permanently damage the cable’s interior.
Dress the cables neatly with cable ties, using low to moderate pressure. Do not over tighten the
ties.
Cross-connect cables where necessary, using rated punch blocks, patch panels and
components. Do not splice or bridge the cable at any point.
Keep the UTP cable as far away as possible from potential sources of EMI, such as electrical
cables, transformers and light fixtures. Do not tie the cables to electrical conduits or lay the
cables on electrical fixtures.
Always test every installed segment with a cable tester. “Toning alone is not an acceptable
test.
Always install jacks so as to prevent dust and other contaminants from settling on the
contacts. The contacts of the jack should face up on the flush mounted plates, or
left/right/down on surface mount boxes.
Always leave extra slack on the cables, neatly coiled in the ceiling or nearest concealed
location. Leave at least five feet at the work outlet side and 15 feet at the patch panel side.
Choose either 568A or 568B wiring standard before beginning. Wire all jacks and patch panels
for the same wiring scheme. Don’t mix 568A and 568B wiring in the same installation.
Always obey all local and national fire and building codes. Be sure to firestop all the cables that
penetrate a firewall. Use plenum rated cable where it is required.
Vertiv | Vertiv™ Avocent® MergePoint Unity™ Switch for Del Installer/User Guide | 64

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv Avocent MergePoint Unity and is the answer not in the manual?

Vertiv Avocent MergePoint Unity Specifications

General IconGeneral
BrandVertiv
ModelAvocent MergePoint Unity
CategorySwitch
LanguageEnglish

Related product manuals