To change device operation:
1. Click the Operation icon.
2. Select the operation to perform:
• On/Off - turns on or off all outlets.
• Reboot - for outlets currently on, reboot cycles the outlets off, then back on after the
reboot hold delay. For outlets currently off, reboot turns the outlets on.
• Cancel - cancels the current operation if it has not been completed.
• Reset Energy - resets the total energy measured in kWh.
• Reset Min Max Values - resets all Min and Max values for current and voltage
measurements.
• Restore Defaults - restores device settings to their factory default. This includes Labels,
Delays and Power-On Actions for the device.
NOTE: These actions affect the entire device.
3. For operations involving the state of the outlets, setting Delay to True uses the current Delay
configuration for each outlet when performing the selected operation.
4. Select Submit to issue the action.
NOTE: Power-on action delays reference the time since the unit was plugged in, not the time since it
fully booted. They may execute before the unit fully boots.
To change phase operation:
1. Click the Operation icon.
2. Select the operation to perform.
• Reset Energy - resets the total Energy measured in kWh for the selected phase.
• Reset Min Max Values - resets Min and Max values for voltage and current.
3. Select Submit to issue the action.
To configure an outlet:
1. Click the outlet configuration icon.
2. Change the configurations, as needed.
a. Label of the outlet.
b. State - the outlet's current state (On or Off).
c. Pending State - the state the outlet is currently transitioning to.
d. Time To Action - the time left before the pending action takes place. This is adjusted
using Delays.
e. On Delay - the time, in seconds, the unit waits before switching an outlet on.
f. Off Delay - the time, in seconds, the unit waits before switching an outlet off.
g. Reboot Delay - the time, in seconds, the unit waits before rebooting an outlet.
3 Setup
27