Symptom Possible Cause Check or Remedy
Reheatwill notoperate; contactor not
pullingin
Control not calling
forheat
Check monitor status.
Reheatsafety stat
open
Jumper betweenterminalsP34-1 andP34-2. If reheat operates, safety isopen. Remove
jumper. Replace safety.
Reheatnotoperating, contactor
pullingin
Heaterburnedout Turnoff power andcheck heatercontinuity withOhmmeter.
Table 10.4 Reheat troubleshooting