Settings based on backup time
Control outlets based on battery backup time remaining.
Threshold of turning off the outlet (min)
When the selected amount of time remains on battery mode, the outlet is turned off.
Select the checkbox to enable or disable (default) the option.
• 0 - 30 minutes (default of 5)
Turn on when power returns for (min)
Length of time after the mains input power returns before turning on the outlet. Select
the checkbox to enable or disable (default) the option.
• 0 - 30 minutes (default of 0)
Settings based on capacity
Control outlets based on battery capacity remaining.
Threshold of turning off the outlet (%)
When the selected percentage of capacity remains in battery mode, the outlet turns off.
Select the checkbox to enable or disable (default) the option.
• 20 - 80 % (default of 20)
Turn on when power returns for (min)
Length of time after the mains input power returns before turning on the outlet. Select
the checkbox to enable or disable (default) the option.
• 0 - 30 minutes (default of 0)