Vertiv | Liebert® GXT RT+ | Installer/User Guide 25
Chapter 6: Specifications
Table 6-1 UPS Specifications
CAPACITY 1000 VA/ 900 W 1500 VA/ 1350 W 2000 VA/ 1800 W 3000 VA/ 2700 W
GXTRT- 1000IRT2UXL 1500IRT2UXL 2000IRT2UXL 3000IRT2UXL
INPUT
Voltage
Range
Low Line Transfer
180 VAC / 160 VAC / 140 VAC / 120 VAC ± 5%
(Ambient Temp. < 35 °C)
(Based on load percentage 100% - 80% / 80% - 70% / 70% - 60% / 60% - 0%)
Low Line Comeback
195 VAC / 175 VAC / 155 VAC / 135 VAC ± 5 %
(Ambient Temp. < 35 °C)
(Based on load percentage 100% - 80% / 80% - 70% / 70% - 60% / 60% - 0%)
High Line Transfer 300 VAC ± 5 %
High Line Comeback 290 VAC ± 5 %
Frequency Range 40 Hz ~ 70 Hz
Phase Single phase with ground
Power Factor 0.95 @ nominal input voltage
OUTPUT
Output Voltage 220/230/240 VAC
Output Power Factor 0.9
AC Voltage Regulation ± 1% (Batt. Mode)
Frequency Range 47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range)
Frequency Range (Batt. Mode) 50 Hz ± 0.5% or 60 Hz ± 0.5%
Overload in Online Mode
Ambient Temp. < 35 °C:
< 105%: Operate continuously
105% - 110%: Transfer to bypass after 10 minutes
110% - 130%: Transfer to bypass after 1 minute
> 130%: Transfer to bypass after 3 seconds
Ambient Temp. > 35 °C:
Derate above times 50%
Overload in Battery Mode
Ambient Temp. < 35 °C:
< 105%: Operate continuously
105% - 110%: UPS shuts down after 10 minutes
110% - 130%: UPS shuts down after 1 minute
> 130%: UPS shuts down after 3 seconds
Ambient Temp. > 35 °C:
Derate above times 50%
Overload in bypass Mode
< 110%: Operate continuously
110% - 120%: UPS shuts down after 30 minutes
120% - 130%: UPS shuts down after 10 minutes
130% - 150%: UPS shuts down after 1 minute
> 150%: UPS shuts down immediately
Transfer
Time
AC Mode to Batt. Mode Zero
Inverter to Bypass 4 ms (Typical)
Waveform Pure Sinewave
EFFICIENCY
Online Mode 88% 88% 89% 90%
Battery Mode 83% 84% 87% 88%