Vertiv | Liebert® GXT5™ | Installer/User Guide 41
3.6. Shutting-down the UPS Completely
WARNING! Risk of electric shock
Can cause injury or death. Disconnect all local and remote electric power supplies before working with
the UPS. Ensure that the unit is shut down and power has been disconnected before beginning any
maintenance.
For 5-kVA to 10-kVA models, transfer to Bypass mode, see Transferring from Normal to Bypass Mode on previous
page. Then, if power to the load is not needed, open the MCB.
For systems with direct power distribution, isolate the UPS from AC power by disconnecting the external- input
MCB. If the main and bypass are independently powered, close the two input MCBs.
3.7. Remote Emergency Power-o (REPO)
REPO turns o the UPS in emergency conditions such as re or ood. When an emergency occurs, the REPO
switch turns o the rectier and inverter and stops powering the load immediately. The battery stops charging
and discharging.
To manually power-o in an emergency, disconnect the terminal connecting the REPO port on the rear of the
UPS.
If mains/utility power is present, the UPS control circuit remains active even though output power is disabled. To
remove all mains/utility power, disconnect the external main-input MCB.