Liebert HPM --- A/W/F/D/H
2.1.7 --- Constant K/L
Refrigeration circuit
All models are provided with a single refrigeration circuit.
The compressor (1) pumps the hot gas eous refrigerant into
an outdoor air---cooled condenser (2). The liquefied refriger-
ant arrives to a liquid receiver (3) that ensures a constant and
even refrigerant flow to the thermostatic expansion valve (4)
and then arrives to the eva porator (5). H ere the refrigerant,
thanks to the heat --- exchanged with the room air moved by
the fan (6) --- evaporates and returns to the compressor (1);
from this, the refrigerant begins a new refrigeration cycle. To
maintain the correct refrigerant discharge pressure, the
speed of th e m otor f an (8) i s con trolled (on---of f or propor-
tional mode).
When the cooling capacity of the room unit is higher than the
room load and the room temperature tends to decrease, the
hot gas valve (11) o pens and the hot gas coil (10) heats the
treated air, maintaining the room at the requested restricted
temperature conditions.
Shut---off valves are provided as standard to assist wit h
routine maintenance.
The compressor (1) has abuilt---in non---returnvalve toavoid
return of liquid ref rigerant from the conden ser in summer-
time, thus protecting the compressor from undesired refri-
gerant slugging during the start up. A second non---return
valve (7) is recommende d to avoid --- in wintertime --- refri-
gerant migration from the liquid pipes and the receiver (3) to
the cond en ser (2), th at sh ould b e resp on sib le of low pres-
sure intervention at the start---up of compressor.
For safety reason, a relief valve (9) is installed on the liquid
receiver (3); this valve is equipped with flanged connections
so that the refrigerant may be discharged to the outside.
SxxKA
MxxKA
Units
1
2
3
9
4
8
7
6
10
5
11
SxxKW
MxxKW
Units
Co o ling Wat er
1
2
3
9
8
5
6
7
10
11
4