EasyManua.ls Logo

Vertiv Liebert S600D - Page 32

Vertiv Liebert S600D
102 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
S600D
31
Figure 3-4 3-in 1-out, common input configuration cable connection (factory default)
2.
3-in 1-out, split bypass configuration
Refer to Figure 3-5, remove the three copper shorting bars between the rectifier input terminals (mA-mB-mC) and
the bypass input terminals (bA-bB-bC). Connect the rectifier input cables to the rectifier input terminals (mA-mB-
mC) in the cabinet, and connect the bypass input cables to the bypass input terminals (bA-bB-bC) in the cabinet.
Connect the input neutral line to the terminal N in the cabinet. Make sure that the phase rotation is correct.
Figure 3-5 3-in 3-out, split bypass configuration cable connection
3.
3-in 1-out, common input configuration
For more details, refer to 8.2.7 .
4.
3-in 1-out, split bypass configuration
For more details, refer to 8.2.7 .
Connecting the system output
In the case of 3-in 1-out configurations, connect the system output cables between the output terminals (oA-oB-oC-
oN) and the load; whereas, in the case of 3-in 1-out configurations, connect the system output cables between the
Note
Note that the common input copper shorting bars are fitted before delivery.

Table of Contents