NetSure
Control Unit (NCU)
User Manual, UM1M830BNA
Spec. No: 1M830BNA, 1M830DNA Code: UM1M830BNA
Model No: M830B, M830D Revision M, May 12, 2017
[185]
Table 7
psBatteryEntry
Battery measurement table entry.
R
psBatteryIndex
Automatically generated index object.
R
psBatteryCurrent
Battery current in amps.
R
psBatteryName
Battery shunt name.
R
psInput Group
psInputLineAVoltage
The AC line A voltage, stored as mV.
R
psInputLineBVoltage
The AC line B voltage, stored as mV.
R
psInputLineCVoltage
The AC line C voltage, stored as mV.
R
psTemperature Group
psTemperature1
The first route temperature, stored as 0.001 Celsius degree.
R
psTemperature2
The second route temperature, stored as 0.001 Celsius degree.
R
Temperature Table
psTemperatureTable
Temperature measurement table.
R
psTemperatureEntry
Temperature measurement table entry.
R
psTemperatureIndex
Temperature probe number.
R
psTemperatureMeasurement
Temperature value in centigrade.
R
psTemperatureName
Configured temperature probe name.
R
psTemperatureType
Temperature Probe Type.
(1) none
(2) ambient
(3) battery
R
psTemperatureAlarmStatus
Temperature Probe Alarm Status.
(1) high
(2) low
(3) fail
(4) none
R
psStatusCommunication
The status of communication with the Power System.
(1) unknown
(2) normal
(3) interrupt indicates some errors occurred between Power System and agent
R