[184]
Table 7. Contents of the Controller’s MIB
Table 7
Ident Group
identManufacturer
The name of the equipment manufacturer.
R
identModel
The manufacturers model designation of the power system.
R
identControllerFirmwareVersion
The firmware (software) version of the controller.
R
identName
The name of the power plant. This object should be set by the administrator.
R/W
identSNMPCfgVer
SNMP configuration version.
R
identControllerSerialNumber
Controller serial number.
R
System Group
systemStatus
Status of the complete plant (highest alarm). One of...
(1) unknown - status has not yet been defined
(2) normal - there are no activated alarms
(3) warning - OA, lowest level of 'abnormal' status
(4) minor - A3
(5) major - MA
(6) critical - CA, highest level of 'abnormal' status
(7) unmanaged
(8) restricted
(9) testing
(10) disabled
R
systemVoltage
System voltage, stored as mV.
R
systemCurrent
System current, stored as mA.
R
systemUsedCapacity
Used capacity, stored as percentage of the total capacity.
R
psBattery Group
psBatteryVoltage
Battery voltage, stored as mV.
R
psTotalBatteryCurrent
Battery current, stored as mA.
R
psBatteryCapacity
Calculated capacity, stored as % of the total capacity.
R
psBatteryNominalCapacity
Nominal installed capacity, stored as mAh.
R
Battery Table
psBatteryTable
Battery table.
R