NetSure
Control Unit (NCU)
User Manual, UM1M830BNA
Spec. No: 1M830BNA, 1M830DNA Code: UM1M830BNA
Model No: M830B, M830D Revision M, May 12, 2017
[189]
Table 7
alarmTime
Date and time when event occurred (local time), including timezone if
supported by controller.
R
alarmStatusChange
The type of alarm change. One of...
(1) activated
(2) deactivated
R
alarmSeverity
The severity of the alarm. One of...
(1) warning - OA, lowest level of alarm severity
(2) minor - A3
(3) major - MA
(4) critical - CA, highest level of alarm severity
R
alarmDescription
Free-text description of alarm.
R
alarmType
Alarm type, i.e. an integer specifying the type of alarm.
R
Event
Tra
p
s
alarmTrap
An alarm trap is sent when an alarm occurs (activated) or returns to normal state
(deactivated). Alarm traps are logged in alarmTrapTable. Variables in this trap:
* alarmIndex
The unique sequence number of this alarm trap.
* alarmTime
Date and time when event occurred (local time), including timezone if
supported by controller.
* alarmStatusChange
(1) activated or (2) deactivated.
* alarmSeverity
Integer describing the severity of the alarm.
* alarmDescription
Free-text description of alarm.
* alarmType
Integer indicating type of alarm.
--
alarmActiveTrap
An alarm trap is sent when an alarm occurs (activated). Variables in this trap:
* alarmTime
Date and time when event occurred (local time), including timezone if
supported by controller.
* alarmSeverity
Integer describing the severity of the alarm.
* alarmDescription
Free-text description of alarm.
* alarmType
Integer indicating type of alarm.
--