Filtering (with or without battery): Typical readings were taken at nominal input voltage, nominal output voltage, 50% load, and 25°C
ambient.
a) Voice Band Noise: Complies with Telcordia GR-947-CORE.
1. Typically 17.68 dBrn C-message weighting. Does not exceed 32 dBrn C.
2. Typically 0.200 millivolts psophometric. Does not exceed 1 millivolt psophometric.
b) Wide Band Noise: Complies with Telcordia GR-947-CORE.
1. Typically 45 millivolts peak-to-peak. Does not exceed 200 millivolts peak-to-peak
2. Typically 4.3 millivolts rms. Does not exceed 100 millivolts rms.
2.2 AC Input Ratings
Voltage: Nominal 480 volts AC, single phase, 60 Hz, with an operating range of 260 to 530 volts. Acceptable input frequency range is
45 to 65 Hz.
Safe Voltage: The system can tolerate 600 volts AC without damage.
Total Harmonic Distortion (THD): < 5% from 50% - 100% load.
Inrush Current: Peak does not exceed 1.5 times the steady state peak value of the input current at full load, nominal input voltage, and
for any duration of AC input interrupts. Under the above conditions, standard AC distribution circuit breakers will not trip.