Chapter 3 Web Interface of RDU501
RDU501 Intelligent Monitoring Unit User Manual
Figure 3-136 Access control
When adding a visitor, enter the new IP address in the upper system IP text box, and click the Set button to
complete the configuration.
Note
The system can add up to 3 higher level management platform IP addresses.
3.
SNMP setting
Click the Network Settings submenu under the System Settings menu, then click the SNMP Settings tab to
configure the SNMP agent. The SNMP agent of the RDU501 system supports both V2 and V3 versions:
As shown in Figure 3-137, the SNMP V2 can be set as follows:
1)
Set the NMS IP (host IP address of the SNMP agent data receiving end);
2)
Set whether to send Trap: “Enable” or “Disable”;
3)
Other parameters remain at their default values.
Figure 3-137 SNMP (V2) settings
As shown in Figure 3-138, the SNMP V3 can be set as follows:
1)
Set the NMS IP (host IP address of the SNMP agent data receiving end);
2)
Select whether to send Trap: “Enable” or “Disable”;
3)
Set the Username;
4)
Select the User type: "Authentication and Encryption";
5)
Select the Authentication type: "MD5", "SHA";
6)
Select the Encryption type: "DES";
7)
Customize the password for the authentication algorithm and encryption algorithm.