Dawn MartinSep 13, 2025
How to fix air leaks from the upper chamber seal of Victaulic FireLock 756 Control Unit?
- CcastillomichelleSep 13, 2025
If air leaks from the upper chamber seal while pushing down on the auto vent during setup, it could be that the adjustment nut on the vent seal is set too low or the vent seal is torn. While the system is pressurized with air, pull up on the auto vent. Turn the adjustment nut under the vent seal clockwise while gently holding down the vent seal. Continue turning the adjustment nut slowly until the vent seal seals. Then, turn the vent seal 1/8 of a turn more counterclockwise. Contact Victaulic.