INSTALLER SAFETY INSTRUCTIONS
WARNING
• Anexperienced,trainedinstallermustinstall
thisproductinaccordancewithallinstruc-
tions.Theseinstructionscontainimportant
information.
• Depressurizeanddrainthepipingsystem
beforeattemptingtoinstall,remove,adjust,
ormaintainanyVictaulicpipingproducts.
Failuretofollowtheseinstructionscancause
productfailure,resultinginseriouspersonal
injuryand/orpropertydamage.
GENERAL
1. Readandunderstandallinstructionsandrefertothetrim
diagramsbeforeproceedingwiththeinstallation,maintenance,
andtestingofthisVictaulicSeries769FireLockNXTPreaction
ValvewithAutoConverttrim.
2. Inspecttheshipment. Make sure all components are included in
the shipment and that all necessary tools are available for installa-
tion.
3. Useonlyrecommendedaccessories. Accessories and equipment
that are not approved for use with this valve may cause improper
system operation.
4. Wearsafetyglasses,hardhat,footprotection,andhearing
protection. Wear hearing protection if you are exposed to long
periods of noisy job-site operations.
5. Preventbackinjury. Larger and pre-trimmed valves are heavy and
require more than one person or mechanical lifting equipment to
position and install the assembly. Always practice proper lifting
techniques.
6. Avoidusingelectricallypoweredtoolsindangerousenviron-
ments. When using electrically powered tools for installation, make
sure the area is moisture-free. Keep the work area well lit, and
allow enough space to accommodate proper installation of the
valve, trim, and accessories.
7. Watchforpinchpoints. Do not place fingers under the valve
body where they could be pinched by the weight of the valve. Use
c aution around spring-loaded components (i.e. clapper assembly).
8. Keepworkareasclean. Cluttered areas, benches, and slippery
floors can create hazardous working conditions.
9. PROTECTTHESYSTEMFROMFREEZINGCONDITIONS.THE
VALVEANDSUPPLYPIPINGMUSTBEPROTECTEDFROM
FREEZINGTEMPERATURESANDMECHANICALDAMAGE.
10. IFTHEINLETWATERSUPPLYISINTERRUPTEDFORANY
REASON,ANDSYSTEMSUPPLYPRESSURETOTHEVALVE
DECREASES,MAKESURETHEDIAPHRAGMCHARGELINEIS
FULLYPRESSURIZEDBEFOREPLACINGTHESYSTEMBACK
INSERVICE.
MAINTENANCEANDTESTING
1. Notifytheauthorityhavingjurisdiction. Always notify the author-
ity having jurisdiction before performing any maintenance that
eliminates the fire protection provided by the system.
2. FollowNFPArequirementsforsystemtestingandinspection
schedules. The building owner or their representative is responsi-
ble for inspecting the system in accordance with current NFPA-25
requirements or in accordance with the requirements of the local
authority having jurisdiction (whichever is more stringent).
3. Depressurizeanddrainthesystemcompletelybeforeperforming
anymaintenance. Water under pressure can cause the cover plate
to blow off during removal if the system is not depressurized and
drained completely.
4. Protectthevalvefromfreezingtemperatures,foreignmatter,
andcorrosiveatmospheres. Any condition that might degrade the
system or affect system performance must be avoided.
INTRODUCTION
The following instructions are a guide for proper installation of Victaulic
Series 769 FireLock NXT Preaction Valves with AutoConvert Trim. These
instructions involve pipe that is properly prepared and grooved in accor-
dance with current Victaulic specifications.
NOTICE
• Drawingsand/orpicturesinthismanualmaybeexaggeratedfor
clarity.
• Thisproductandthisinstallation,maintenance,andtesting
manualcontaintrademarks,copyrights,and/orpatentedfeatures
thataretheexclusivepropertyofVictaulic.
I-769P.AC/ELEC_2
FireLockNXT™AutoConvertPreactionValve
SERIES 769
PreactionElectricAutoConvertDryTrim
I-769P.AC/ELEC
INSTALLATION,MAINTENANCE,ANDTESTINGMANUAL
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.
REV_B