52
6 "Minimum heating output"
Setting Explanations
A limit can be set on the minimum heating output for
heating mode.
... Delivered condition specified by settings specific to
the appliance
0 to 100 Adjustable from 0 to 100 %
7 "Maximum heating output"
Setting Explanations
A limit can be set on the maximum heating output for
heating mode.
100 Heating output in the delivered condition 100 %
0 to 100 Adjustable from 0 to 100 %
8 "Maximum flow temperature limit, heating circuit 1"
Setting Explanations
Maximum flow temperature limit for the heating circuit
Maximum limit in the delivered condition 82 °C
Setting range limited by heat generator-specific pa-
rameters
Energy saving functions (setting only via software tool)
2426.1 Weather-compensated heating circuit pump logic function (only for weather-compensated control
units).
Setting Explanations
If the outside temperature is above the threshold val-
ue (the selected set room temperature plus the hyste-
resis in K), the heating circuit pump is switched off.
If the outside temperature is below the threshold value
(selected set room temperature plus hysteresis in K),
the heating circuit pump is switched on.
2426.3 Room temperature-dependent heating circuit pump logic for heating circuit 1 (only for weather-
compensated control units).
Setting Explanations
If the actual room temperature is above the threshold
value (selected set room temperature plus offset in K),
the heating circuit pump is switched off.
If the actual room temperature is below the threshold
value (selected set room temperature plus offset in K),
the heating circuit pump is switched on.
1667.0 Pump activation, heating circuit pump in standby mode (via software tool)
Setting Explanations
Operating mode, heating circuit pump
0 In "Standby mode" = permanently switched off
1 to 24 When in "Standby mode", switched on 1 to 24 times a
day for 10 min in constant operation and for 50 min in
weather-compensated mode
System configuration (parameters)