Displayed fault
code
System characteristics Cause Measures
7 No DHW heating Lead break, cylinder tem-
perature sensor
Check DHW setting in the com-
missioning assistant and correct
if necessary.
Check the cylinder temperature
sensor (terminal S.T.S).
Measure voltage at sensor input
on HBMU heat management
unit. Set value: 3.3 V with sen-
sor disconnected
Replace faulty component if neces-
sary.
8 No DHW heating Short circuit, cylinder tem-
perature sensor
Check the cylinder temperature
sensor (terminal S.T.S).
Replace faulty component if neces-
sary.
13 Regulates as if the outside
temperature were 0 °C.
Lead break, outside tem-
perature sensor
Check operating mode setting in
commissioning assistant and
remedy if necessary.
Check the outside temperature
sensor and connection to sensor
(terminal O.T.S).
Measure voltage at sensor input
on HBMU heat management
unit. Set value: 3.3 V with sen-
sor disconnected
Replace faulty component if neces-
sary.
14 Regulates as if the outside
temperature were 0 °C.
Short circuit, outside tem-
perature sensor
Check the outside temperature
sensor and connection to sensor
(terminal O.T.S). Replace faulty
components if necessary.
49 Burner in a fault state Lead break, flue gas tem-
perature sensor
Check flue gas temperature sen-
sor.
Reset the appliance.
50 Burner in a fault state Short circuit, flue gas tem-
perature sensor
Check flue gas temperature sen-
sor.
Reset the appliance.
57 Normal operation without
room influence
Lead break, room temper-
ature sensor
Check commissioning setting of
remote control.
Check plug and cable of external
room temperature sensor, heat-
ing circuit.
If no external room temperature
sensor installed, replace pro-
gramming unit.
58 Normal operation without
room influence
Short circuit, room tem-
perature sensor
Check plug and cable of external
room temperature sensor, heating
circuit.
If no external room temperature
sensor installed, replace program-
ming unit.
59 Burner locked out, boiler cir-
cuit pump off. No central
heating, no DHW heating
Power supply, undervolt-
age
Check mains voltage.
If voltage is correct and the fault
occurs repeatedly, replace the fan
unit.
Troubleshooting
Fault messages (cont.)
6179762
Diagnosis