Displayed fault
code
System characteristics Cause Measures
352 Burner in a fault state Combustion CO limit ex-
ceeded
Check entire flue gas path for the
following:
Leaks
Flue gas back pressure caused
by water pocket (if flue system
fall is insufficient)
Constrictions
Blockages
Repair flue system if necessary.
Reset the appliance.
353 Shutdown with restart if de-
mand exists
Insufficient gas supply,
burner output reduced
Check the gas supply.
Visually inspect gas solenoid valve
inlet strainer for contamination.
Reset the appliance.
354 Burner in a fault state Gas modulation valve tol-
erance outside permissi-
ble range
Replace gas fan unit.
355 Burner in a fault state Analogue signal reference
check: Flame signal is al-
ready present at burner
start.
Replace the HBMU heat manage-
ment unit. See chapter "Replacing
the HBMU heat management unit".
359 Burner in a fault state No ignition spark
Check whether the ignition elec-
trode insulation is damaged.
Check for a voltage of 230 V at
the ignition module during the ig-
nition phase. If not, replace the
HBMU heat management unit.
If 230 V~ is present at the igni-
tion module but there is still a
fault, replace the ignition module.
Check connecting cables and
leads from ignition module and
ignition electrode.
Reset the appliance.
361 Burner in a fault state Flame signal is not
present or insufficient at
burner start.
Check ionisation electrode and
connecting cable. Check plug-in
connections for loose contacts.
Note
Deposits on the electrodes indicate
foreign bodies in the combustion
air. Check the installation room and
flue system for causes of the de-
posits. For example: Laundry de-
tergents, cleaning agents, toilet-
ries, deposits in the ventilation air
supply (chimney)
Reset the appliance.
364 Burner in a fault state Internal fault. Replace the HBMU heat manage-
ment unit.
365 Burner in a fault state Gas valve relay contact
feedback implausible (re-
lay contact is "welded up")
Replace the HBMU heat manage-
ment unit.
Troubleshooting
Fault messages (cont.)