EasyManua.ls Logo

Viessmann Vitocal 252-A Series - Page 107

Viessmann Vitocal 252-A Series
212 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
107
Note
For indoor units with 2 integrated heating/cooling cir-
cuits, heating/cooling circuit 2 is filled in the 1st step.
Then the filling of the rest of the system, including the
outdoor unit, is menu-guided. For this, the 4/3-way
valve switches in turn between each of the lines for the
heating/cooling circuit 1, DHW heating, defrost buffer,
etc.
Filling heating/cooling circuit 2
Note
Only for indoor units with 2 integral heating/cooling cir-
cuits
2
2
Fig. 74
1. Call up the filling function in the commissioning
assistant.
2. Connect the fill hose to the 3-way ball valve, heat-
ing/cooling circuit 2 flow.
3. Connect the drain hose to the 3-way ball valve,
heating/cooling circuit 2 return. Route the hose into
a suitable container or drain outlet.
4. Open the 3-way ball valves in the heating/cooling
circuit 2 flow and return as shown in Fig. 74.
Allow the heating water to flow in via the fill hose.
Required flow rate for filling with heating water:
Min. 600 l/h
Max. 1500 l/h
Filling pressure: 0.3 to 0.5 bar (30 to 50 kPa)
higher than diaphragm expansion vessel pre-
charge pressure
Factory-set pre-charge pressure of expansion ves-
sel: 0.75 bar (0.075 MPa) to 0.95 bar (0.095 MPa)
5. Start the filling process in the commissioning assis-
tant.
6. As soon as air bubbles are no longer coming out of
the drain hose, end the filling with .
The commissioning assistant switches to filling the
remaining consumer circuits.
7. Close both 3-way ball valves.
8. Remove the fill and drain hoses.
Commissioning, inspection, maintenance
Filling the system (cont.)
6222080

Table of Contents

Related product manuals