Danger
Escaping refrigerant can lead to explosions that
result in very serious injuries.
Do not introduce any power sources or ignition
sources into the safety zone.
Complete units and compressors are only to
be disposed of via qualified disposal special-
ists.
In the case of damage to the refrigerant circuit
or suspected leakage from the refrigerant cir-
cuit, evacuate the refrigerant circuit. Fill with
nitrogen or comparable gases.
Observe the following regulations:
Fluorinated greenhouse gas regulation 517/2014/EU
Currently applicable regulations and requirements
Note
Before commencing decommissioning, note the
"Checklist for maintenance work" on page 165.
Decommissioning:
Positioning requirements apply only so long as the
outdoor unit is filled with refrigerant: See page 23.
Decommissioning may only be carried out by a quali-
fied contractor who is familiar with the equipment
used for refrigerant disposal.
For decommissioning and disposal also, work on the
refrigerant circuit may only be carried out by qualified
and certified personnel: See "Safety information".
Check that it is possible to transport the outdoor unit
safely. If necessary, extract the refrigerant: See
chapter "Extracting the refrigerant" on page 177.
Frost protection:
To avoid frost damage, completely remove heating
water from the connection pipes and the condenser
(not required with frost-free storage).
Intermediate storage:
Intermediate storage only above ground level with
natural ventilation aperture to the outside
Ensure adequate air circulation during intermediate
storage.
If the outdoor unit dismantled for disposal is not
stored in accordance with the siting requirements,
the following steps must be carried out:
Check that it is possible to transport the outdoor unit
safely. If necessary, extract the refrigerant: See
chapter "Extracting the refrigerant" on page 177.
Transport:
Observe transport information: See page 23.
Observe all applicable regulations and requirements.
Note
According to the European regulation on the carriage
of dangerous goods by road (ADR), special regula-
tion 291 for transporting complete units with less
than 12 kg of flammable refrigerant, no special trans-
port requirements need be followed.
Transport only in an upright position
Use suitable transport brackets.
Ensure adequate air circulation during transport.
Keep ignition sources away, e.g. flying sparks, smok-
ing, etc.
Appendix