95
Function Code Operat-
ing level
Setting options Delivered
condition
"End - room temp - re-
duced setpoint - in-
crease"
801 "F2" -30 to 10 °C -14
"Frost prot plant HC
pump"
810 "F2" "Off"
"On"
"On"
"Mixer setpoint boost"
(differential temperature)
830 "F1" 0 to 50 °C 8
"Actuator running time" 834 "F2" 30 to 873 s 120
"Screed drying func-
tion" (see page 83)
850 "F2" "Off"
"Functional
heating"
"Curing heat-
ing"
"Functional +
curing heat-
ing"
"Curing +
functional
heating"
"Manually"
"Off"
"Floor curing setp man-
ually"
851 "F2" 0 to 95 °C 25
"Flow temp setpoint
screed drying"
855 "F2" 0 to 95 °C 0
"Screed drying day" 856 "F2" 0 to 32 days 0
"Floor curing days com-
pleted"
857 "F2" 0 to 32 days 0
"Heating circuit 1 with
buffer"
The heating circuit is con-
nected to a heating water
buffer cylinder.
870 "F2" "No"
"Yes"
"Yes"
Codes
Changing codes
(cont.)
5618 294 GB
Service