94
Function Code Operat-
ing level
Setting options Delivered
condition
"Flow temp setpoint
min"
740 "F2" 8 to 95 °C 20
"Flow temp setpoint
max"
741 "F2" 8 to 95 °C 80
"Room temperature in-
fluencing factor"
750 "F2" - - -/0 to 100 % 0
"Type room controller"
(see page 160)
759 "F2" "Manually"
"Radiator
fast"
"Radiator me-
dium"
"Radiator
slow"
"Floor heat
fast"
"Floor heat
medium"
"Floor heat
slow"
"Radiator
medium"
"Room temp limitation" 760 "F2" - - -/0.5 to 4.0 °C 2.0
"Quick setback" (setback
mode)
780 "F2" "Off"
"Down to re-
duced set-
point"
"Down to frost
prot setpoint"
"Down to re-
duced set-
point"
"Opt start max opt ener-
gy" with optimum energy
(see page 153)
789 "F2" 0 to 480 min
(00:00:00 -
00:80:00)
240
"Start optimisation max.
advance" (see
page 153)
790 "F2" 0 to 360 min
(00:00:00 -
00:06:00)
0
"Optimum stop control
max. advance" (see
page 153)
791 "F2" 0 to 360 min
(00:00:00 -
00:06:00)
60
"Start - room temp - re-
duced setpoint - in-
crease"
800 "F2" - - -/-30 to 10 °C -5
Codes
Changing codes
(cont.)
5618 294 GB