97
Function Code Operat-
ing level
Setting options Delivered
condition
"Type room controller"
(see page 160)
1059 "F2" ■ "Manually"
■ "Radiator
fast"
■ "Radiator me-
dium"
■ "Radiator
slow"
■ "Floor heat
fast"
■ "Floor heat
medium"
■ "Floor heat
slow"
"Radiator
medium"
"Room temp limitation" 1060 "F2" - - -/0.5 to 4.0 °C 2.0
"Quick setback" (setback
mode)
1080 "F2" ■ "Off"
■ "Down to re-
duced set-
point"
■ "Down to frost
prot setpoint"
"Down to re-
duced set-
point"
"Opt start max opt ener-
gy" (see page 153)
1089 "F2" 0 to 480 min
(00:00:00 -
00:80:00)
240
"Start optimisation max.
advance" (see
page 153)
1090 "F2" 0 to 360 min
(00:00:00 -
00:06:00)
0
"Optimum stop control
max. advance" (see
page 153)
1091 "F2" 0 to 360 min
(00:00:00 -
00:06:00)
60
"Start - room temp - re-
duced setpoint - in-
crease"
1100 "F2" - - -/-30 to 10 °C -5
"End - room temp - re-
duced setpoint - in-
crease"
1101 "F2" -30 to 10 °C -14
"Frost prot plant HC
pump"
1110 "F2" ■ "Off"
■ "On"
"On"
"Mixer setpoint boost"
(differential temperature)
1130 "F1" 0 to 50 °C 8
"Actuator running time" 1134 "F2" 30 to 873 s 120
Codes
Changing codes
(cont.)
5618 294 GB
Service