Safety Connections and Pressure Testing (Continued)
Perform pressure test on the boiler
The boiler must be leak test ed before
being placed in operation. Before boiler
is connected to piping or electrical
power supply, it must be hydrostatically
pressure tested with a maximum of 1½
times the maximum operating pressure
of the boiler.
1. After installing safety devices
(above), install temporary cap on ¾”
nipple extension (nipple for pressure
relief valve mounting).
2. Cap supply and return connections.
3. Connect ½” garden hose to boiler
drain valve and fill boiler slowly until
pressure gage indicates max. 45 psi /
310 kPa.
4. Maintain pressure for 15 minutes.
During time of pressure testing, do
not leave boiler unattended.
5. Inspect all pipe joint connections, the
safety devices (Safety Header, if
applicable), and boiler base with
flashlight for leaks.
6. After 15 minutes, release water
pressure from boiler by opening boiler
drain valve slowly, remove caps from
supply and return connections as
well as ¾” cap from safety nipple,
and install pressure relief valve
immediately instead of ¾” cap.
After boiler has passed pressure test,
proceed with installation.
Max. operating pressure
30 psig / 207 kPa
.......................................
Max. testing pressure
45 psig / 310 kPa
.......................................
Max. boiler temperature
248°F / 120°C
............................................
In all provinces where a CRN is not
required, and in the USA:
H the max. operating pressure is
45 psig / 310 kPa
H the max. testing press ure is
68 psig / 465 kPa.
DHW Connections
Installation Instructions
Domestic Hot Water Storage Tank
5285 838 v2.1
Exposing the boiler to pressures and
temperatures in excess of those lis ted
will result in damages, and will render
warranty null and void.