Manual BG41/BG42/BG43 Software
Rev. 99/49 4-69
The data handling block examines the parametrized values at the following limits:
ADRE F080...F1FC
SSNR 1...2 (3)
A-NR 1...255
QTYP DB,DX,EB,AB,MB,T,Z
QDBN 2...255
QBWN depending on source type (0...)
BWAN depending on source type (1...)
ZTYP DB,DX,EB,AB,MB,T ,Z .
ZDBN 2...255
ZBWN depending on target area (0...)
The target area must be at least as long as that given by means of the operands
BWAN and ZBWN.
ANZW no examination
PAFE no examination
NEUS no examination
Example: FB23, (SEND) by direct parametrizing
:
:SPA FB23
NAME :SEND
ADRE : KH F080 Address set with DIL switches
SSNR : KF +1 Interface number 1,2 (3)
A-NR : KF +4 Order number (1...255)
QTYP : KC MB Source type
QDBN : KY 0,0 DB no. by source type DB
QBWN : KY 0,100 From Data in the source type
BWAN : KF 10 Amount of data to be sent (bytes/words depending on source
type)
ZTYP : KC DB Target type
ZDBN : KY 0,5 DB no. by target type DB
ZBWN : KY 0,20 Telegram to be filed from DB 20 in target
KOOR : KY 20.3 Coordination flag in target PLC
ANZW : MW 30 The display word is filed in this word
PAFE : MB 32 Error messages in relation to parametrizing are filed in this
byte
NEUS : M 1.0 New start bit